The Ultra high performance filter is a superior filter housed in a three compartment casing that achieves 100 dB insertion transmission loss at 14 kHz.
The circuit is designed as a symmetrical double- circuit with high quality rod cores providing inductance. These cores do not saturate due to their large air gap and they are insensitive to asymmetrical load.
Foil capacitors ensure a long operating life by their self healing feature even after voltage transients A seamless fixing of the filter casing to the shielded room is very important to ensure correct operation. The filter is housed in a casing that has a base flange which provides stable mounting and excellent earthing when bolted to the shielded room via the mounting bolts.
This series is offered as a two line filter (phase and neutral) or as a four line filter (three phases and neutral). The neutral line is always attenuated and all conductors are decoupled from each other. This allows the conductors to operate independently without attenuation loss.
Input and output terminals are accessible under high frequency shielding caps. EMP protection is available on request.
Mounting
These variety protections are designed for mounting on the penetration panel or directy on the non-painted wall of the Faraday cage.
General characteristics
For a clean mains supply into a shielded room, high performance filters are indispensable. Usually, these filters are directly mounted on the shielding wall. It is recommended to route filtered lines into the shielded room (Faraday cage) through the wall with an optional flexible metal conduit.
Mains filter for single and three pahse systems
Insertion transmission loss 100 dB @ 14 kHz
Double - ∏ circuit
Rod cores allow asymmetrical load
Self-healing effect of foil capacitors
Technical characteristics
Mains voltage
: 250/440 VAC; 50/60 Hz; 600 VDC
Current rating
: relative to 50 Hz and 40 ºC ambient temperature
Current rating
: 1,4 lN for 15 min
Ambient temperature
: -40 ºC + 40 ºC
Test voltage
: 1200 VDC for 2 s (line / line; line / earth)
Models and ordering data
Order number
rated Current
Type
Number of lines
Voltage drop
Leakage current per line
Approximative weight
(A)
-
-
-
(A)
(Kg)
UHP3 - 2006
6
2 x 6 A
2
1,6 VDC, 2 VAC
0,9
10
UHP3 - 4006
6
4 x 6 A
4
1,6 VDC, 2 VAC
0,9
20
UHP3 - 2010
10
2 x 10 A
2
1,5 VDC, 2 VAC
1,1
10
UHP3 - 4010
10
4 x 10 A
4
1,5 VDC, 2 VAC
1,1
20
UHP3 - 2016
16
2 x 16 A
2
1,5 VDC, 2 VAC
1,7
12
UHP3 - 4016
16
4 x 16 A
4
1,5 VDC, 2 VAC
1,7
24
UHP3 - 2025
25
2 x 25 A
2
1,0 VDC, 2 VAC
2,5
14
UHP3 - 4025
25
4 x 25 A
4
1,0 VDC, 2 VAC
2,5
28
UHP3 - 2040
40
2 x 40 A
2
1,0 VDC, 2 VAC
3,5
19
UHP3 - 4040
40
4 x 40 A
4
1,0 VDC, 2 VAC
3,5
38
UHP3 - 2063
63
2 x 63 A
2
0,7 VDC, 2 VAC
5,9
39
UHP3- 4063
63
4 x 63 A
4
0,7 VDC, 2 VAC
5,9
78
UHP3 -2085
85
2 x 85 A
2
0,6 VDC, 2 VAC
6,4
48
UHP3 - 4058
85
4 x 85 A
4
0,6 VDC, 2 VAC
6,4
96
UHP3 - 2125
125
2 x 125 A
2
0,5 VDC, 2 VAC
8,4
57
UHP3 - 4125
125
4 x 125 A
4
0,5 VDC, 2 VAC
8,4
114
UHP3 - 2200
200
2 x 200 A
2
0,5 VDC, 2 VAC
9,0
66
UHP3 - 4200
200
4 x 200 A
4
0,5 VDC, 2 VAC
9,0
132
For the explanation of the reference see chapter " how to order" below
Attenuation characteristics
Dimensions in mm
Reference
A
B
C
D
E
Drawing Reference
Cable diameter
Terminal thread size
Fixing hole diameter
UHP3 - 2006 UHP3 - 2010 UHP3 - 2016
570
150
102
110
130
Type 3
Ø 22
M 5
Ø 7
UHP3 - 4006 UHP3 - 4010 UHP3 - 4016
570
260
102
110
240
Type 2
Ø 22
M 5
Ø 7
UHP3 - 2025 UHP3 - 2040
780
260
102
150
240
Type 2
Ø 22
M 5
Ø 7
UHP3 - 4025 UHP3 - 4040
780
380
102
150
350
Type 1
Ø 22
M 5
Ø 7
UHP3 - 2063 UHP3 - 2085
1200
350
150
230
300
Type 3
Ø 30
M 8
Ø 11
UHP3 - 4063 UHP3 - 4085
1200
550
150
230
500
Type 2
Ø 30
M 8
Ø 11
UHP3 - 2125 UHP3 - 2200
1500
350
150
290
300
Type 3
Ø 46
M 12
Ø 11
UHP3 - 4125 UHP3 - 4200
1500
550
150
290
500
Type 2
Ø 46
M 12
Ø 11
* For the explanation of the reference see chapter " how to order " below
Example
The picture below explaines how to generate a Ultra high performance part number. - Serie (UHP3 = Ultra high performance type 3); - the amount of phases; - the current (A); - and then the amount of volts (250/400).
Serie
Phases
Current (A)
Volts
UHP3
2
125
250
2 : Single phase + N 4 : Three phase + N
Specify the wanted current
250 Volts 400 Volts
Get a price quotation
Do you want to receive a price quotation for Ultra high performace within 24 hours, than please click on the right button.